Landscape Lighting Voltage Drop and Transformer Sizing Calculator
Plan a whole job, one wire run at a time. Create a wire run, set its wire size, length and tap, and add the fixtures on it with their VA. Then add the next run. Each run is calculated on its own, and the system summary sizes the transformer for all of them.
Shop by fixture type: accent lights · path lights · well lights · flood and wash lights · downlights · hardscape lights · step lights · deck lights · bollard lights · underwater lights
Finish the system: landscape lighting wire · transformers · 12V LED lamps
How this voltage drop calculator works
Each fixture's VA is converted to current on a 12 V basis, then the calculator works out how much voltage the cable loses carrying that current out and back.
Voltage drop per section = current × 2 × section length × wire resistance per foot
With All at the end, the full load travels the full distance. That is the worst case, and it also describes a hub, where one home run feeds a junction and short equal leads feed the fixtures.
With Spread along the run, fixtures are spaced evenly and the run is calculated section by section. Each section carries only the fixtures beyond it, so the drop shrinks as you move down the cable. Mixed fixture types are alternated along the run.
Why VA matters more than watts
A transformer and a cable have to supply volt-amps, not watts. LED lamps and integrated fixtures often draw more VA than their wattage suggests, so this calculator asks for the VA on every row. You will find it on the fixture or lamp spec sheet. If only watts are listed, use the wattage and leave extra margin.
What voltage should reach the fixtures?
| Voltage at the fixture | What the calculator shows | What to do |
|---|---|---|
| 12 to 15 V | Preferred | Install as planned, then confirm with a meter. |
| Below 12 V, above the fixture minimum | Review | Check the rated input range. Many LED lamps accept 9 to 15 V, but not all. |
| Above the maximum or below the minimum | Out of range | Change the tap, the wire, the layout or the load. |
Wire resistance used
| Wire | Ohms per 1,000 ft | Planning current limit used here |
|---|---|---|
| 18/2 | 6.385 | 7 A |
| 16/2 | 4.016 | 10 A |
| 14/2 | 2.525 | 15 A |
| 12/2 | 1.588 | 20 A |
| 10/2 | 0.999 | 25 A |
| 8/2 | 0.628 | 25 A |
Resistance is nominal copper at 68°F. Warm soil and warm cable raise resistance, so leave margin. The current limits are conservative planning figures. Your cable and transformer ratings take priority.
Transformer size is a separate calculation
Voltage drop tells you whether a run works. Transformer size tells you whether the whole system has enough capacity. Add the VA of every run, divide by 0.8, and choose the next size up. The system summary does this across all the wire runs you enter.
How to fix a run with too much voltage drop
- Go up a wire size. Open the wire comparison under any run to see what each gauge would do on that exact run.
- Raise the tap. Check that the first fixture stays under its maximum when you do.
- Split the run. Two runs of half the load each drop far less than one.
- Use a hub. One heavy home run to a central junction, with equal leads to each fixture, gives every fixture the same voltage.
Common questions
How do I plan a job with several wire runs?
Add a wire run for each cable leaving the transformer. Give each run its own wire size, length, tap and fixtures. Every run is calculated on its own, and the system summary totals the VA to size the transformer.
Can I mix different brands and fixture types on one run?
Yes, as long as every fixture's rated input range covers the voltage it will see. Add each type as its own row with its own VA.
Is this a substitute for measuring?
No. It is a planning tool. Measure voltage at the first and last fixture with the system fully loaded before you bury the cable.
Does this replace the electrical code or an electrician?
No. Follow the transformer and fixture instructions and your local code, and use a licensed electrician for line-voltage work.